Release Notes

NXB-CCG NetLinx Clear Connect Gateway Build v2.2.2

FG#: FG2606 (NXB-CCG)
     FG2606-868 (NXB-CCG-K)

Current Firmware Version: 2.2.2
Release Date: 5/22/2014

Device Id: N/A

Prerequisites: None.


Changes in this release
-----------------------
-- Added support for CCD-6CL Clear Connect CFL, LED, 600W Incandescent/MLV Dimmer 
-- Increased supported device count from 32 to 64 (including the Gateway)
-- Fixed an issue in log extraction that would cause the transfer to fail if the
   size of the data was greater than ~10KB



Known Issues
------------

-- It is recommended that steps be taken to ensure power to the device does not 
   fail during firmware updating. Power failure during firmware update can result 
   in corruption to the database.
-- Issuing integration commands to control dimmers too quickly (> 5-10 commands per second)
   can cause commands to be dropped and can result in long delays in the Clear 
   Connect system.
-- Making more than 50 simultaneous connections to the CCT can cause the NXB-CCG 
   to become unresponsive. A power cycle of the device will fix the issue.
-- Downgrading the NXB-CCG firmware may delete all programming.
-- Using Zeroconf resolved host names to access the web pages is slow in some browsers. 
   If this is experienced, log out and re-connect to the device using its IP address.
-- CCT requires reboot when changing physical network connection manually (ie. connecting
   cable, removing connection to router and connecting to other router or PC, etc.)
-- An issue was found in which a power cycle of the NXB-CCG during or just after a firmware
   update could cause the unit to not be downgradeable to a previous release.
-- When using Link Local addressing, the DNS servers and domain name shown in the web UI
   may be inaccurate.
-- Login via standards compliant telnet client may fail first login. Subsequent attempts 
   to log in will work properly.
-- When cancelling finding remote addressable shades, it is rare but possible to trigger 
   a condition in which cancel is no longer possible (fails) and you are stuck searching 
   for shades  if this occurs, exit Add Devices and re-enter to clear the error.
-- In very rare instances, the web server may stop responding, displaying The page you 
   are looking for is temporarily unavailable. Please try again later. If this continues 
   for more than 5 minutes, cycle power to the device to clear the error.